Tapstat Cylinder Controls
- Self acting (non electric)
- Range limiting stops
- Remote sensor with 2m capillary
- Compression fittings for copper pipe
- Simple to install
Self-acting tapstats control domestic hot water temperatures on gravity or pumped primary systems preventing scalding and fuel wastage
Technical
| Max. static pressure | 147 psi (10 bar) |
| Max. primary flow temperature | 100°C continuous 120°C intermitte |
Max. differential pressure* | 15mm 2 way 59 psi (4 bar) 15mm 3 way 29 psi (2 bar) 28mm gravity 7 psi (0.5 bar) |
Kv value (fully open) | 15mm 2 way 1.1 15mm 3 way 1.1 28mm gravity 4.6 |
| Setting range | 32°C to 72°C |